KUALITAS AIR BERSIH DI TINJAU DARI PARAMETER PH SISA KLOR DAN MPN COLIFORM DI RSUD BRIGJEN HASAN BASRI KAB. HULU SUNGAI SELATAN TAHUN 2017
ABSTRACT
Scientific Paper
YULIA MIRANTI
DRINKING-WATER QUALITY REVIEWED BASED ON pH, CHLORINE RESIDUAL AND MPN COLIFORM PARAMETERS AT RSUD H. HASAN BASRY, SOUTH HULU SUNGAI DISTRICT 2017
(Munawar Raharja ; H. M. Irfa’i)
xiv+ 44 Pages; 6 Tables; 1 Image; 10 Appendices
Water has important role in the some infectious diseases transmission, so the water quality in the Hospital must meet the quality and quantity requirements. This study aims to describe the drinking-water quality at RSUD H. Hasan Basry, South Hulu Sungai District.
This study was descriptive to describe the drinking-water quality in RSUD and cross sectional design. The study population and sample was all the water reservoir Nutrition Installation taken by grab sampling for physical and chemical parameter with 3 times repetition. Data collection methods were primary and secondary data.
Based on the measurement result obtained pH water of 6.00-6.67. The average of chlorine residual was ≤ 0.1 mg/L. MPN coliform was 0-94.3. Based on the water quality standards that have been established Permenkes No. 416/Menkes/Per/IX/1990 about water quality control requirements on pH standard for the Water Supply Company, Mixture and Nutrition Installation had not met their standards. The MPN Coliform quality standard of water samples on the Water Supply Company, Mixture and Nutrition Installation were exceed their standards. Meanwhile, the chlorine residual of water samples on the Water Supply Company, Mixture and Installation Nutrition were still below their standards. So, it can be concluded that pH of 6.00-6.67, chlorine residual of ≤ 0.1 dan MPN of 0-94.3.
Alternative solutions can be given to their parameters are by appropriate chlorine dose addition.
Keyword : Hospital drinking-water quality
Literature : 18 (1990-2010)
ABSTRAK
Karya Tulis Ilmiah
YULIA MIRANTI
KUALITAS AIR BERSIH DI TINJAU DARI PARAMETER PH, SISA CHLOR DAN MPN COLIFORM DI RSUD H. HASAN BASRY KABUPATEN HULU SUNGAI SELATAN TAHUN 2017
(Munawar Raharja ; H. M. Irfa’i)
xiv +44 halaman;6 tabel ; 1 gambar; 10lampiran
Air mempunyai peranan besar dalam penularan beberapa penyakit menular, maka kualitas air di Rumah Sakit harus memenuhi persyaratan kualitas dan kuantitas. Tujuan penelitian untuk mengetahui gambaran kualitas air bersih di RSUD H. Hasan Basry Kabupaten Hulu Sungai Selatan.
Penelitian ini bersifat deskriptif untuk menggambarkan kualitas air bersih di RSUD dan desain penelitian Cross sectional. Populasi dan sampel pada penelitian yaitu seluruh air bak penampungan Instalasi Gizi yang diambil secara grab samplinguntuk parameter fisika dan kimia dengan pengulangan sebanyak 3 kali. Metode pengumpulan data yaitu data primer dan sekunder.
Berdasarkan hasil pengukuran diperoleh pH air 6.00 - 6,67. Sisa chlor rata-rata ≤ 0,1 mg/L. MPN coliform 0 - 94,3. Berdasarkan standar kualitas air bersih yang ditetapkan Permenkes No. 416/Menkes/Per/IX/1990 tentang syarat-syarat pengawasan kualitas air untuk standar pH maka PDAM, campuran dan Instalasi Gizi belum memenuhi standar. Kualitas MPN coliform pada air PDAM, campuran dan Instalasi Gizi melebihi standar. Sedangkan kualitas sisa chlor untuk air PDAM, campuran, Instalasi Gizi masih dibawah standar. Maka didapatkan kesimpulan yaitu pH 6,00-6,67 sisa chlor ≤ 0,1 dan MPN 0-94,3.
Alternatif pemecahan masalah yang dapat diberikan untuk parameter pH, sisa chlor dan MPN coliform yaitu dengan cara penambahan dosis kaporit yang sesuai.
Kata Kunci :Kualitas Air Bersih Rumah Sakit
Kepustakaan : 18 (1990-2010)